Subscribing to PLC data via code
VB Example:
The AdvancedHMI drivers support a subscription that will automatically poll data and return the values. The DataSubscriber provides a non-code method of using this service. However, there are times when it is desired or more efficient to subscribe using code. This is an example on how to do this:
Private SubscriptionID1 As Integer Private Sub Button2_Click_1(sender As Object, e As EventArgs) Handles Button2.Click SubscriptionID1 = EthernetIPforCLXCom1.Subscribe("MyTag", 1, 500, AddressOf Subscription_DataReceived) End Sub
Private Sub Subscription_DataReceived(sender As Object, e As Drivers.Common.PlcComEventArgs) If e.ErrorId=0 AndAlso e.Values IsNot Nothing AndAlso e.Values.Count>0 Then Label1.Text = e.Values(0) End If End Sub
Private Sub MainForm_FormClosing(sender As Object, e As FormClosingEventArgs) Handles Me.FormClosing EthernetIPforCLXCom1.UnSubscribe(SubscriptionID1) End Sub
The rate at which data is polled is determined by the value of the PollRateOverride property.
Each driver is highly optimized for communications using subscriptions. All of the visual controls (e.g. Gauge) use the subscription mechanism to receive their data.
C# Example:
The Following is an example of how to programmatically set the comm drivers and create subscriptions to PLC addresses using the "DataSubscriber2" control. The "DataSubscriber2" runs on a background thread which allows for asynchronous capability when gathering tag information.
using AdvancedHMIDrivers; using AdvancedHMIControls; using MfgControl.AdvancedHMI.Drivers; using System; using System.Collections.Generic; using System.ComponentModel; using System.Data; using System.Drawing; using System.Linq; using System.Text; using System.Threading.Tasks; using System.Windows.Forms; // namespace AdvancedHMICS { public partial class MainForm : Form { #region Initalize Comms & Properties // Always have 3 Comm Drivers (Slow, Medium, and Fast) // It doesn't slow down your application because this all runs on a background thread // and the comms drivers poll from the same datalink layer EthernetIPforSLCMicroCom CommSlowDewaxer1 = new EthernetIPforSLCMicroCom(); EthernetIPforSLCMicroCom CommMediumDewaxer1 = new EthernetIPforSLCMicroCom(); EthernetIPforSLCMicroCom CommFastDewaxer1 = new EthernetIPforSLCMicroCom(); // // The following variables set the properties of the comms above in the project string CommDewaxerIPAddress = "10.60.48.138"; int CommSlow = 1000; // polling every second int CommMedium = 500; // polling every half second int CommFast = 200; // polling every 200 milliseconds #endregion // #region DataSubscribers bool initalizeSub = false; // Dewaxer 1 Subscribers DataSubscriber2 DataSlowDewaxer1 = new DataSubscriber2(); DataSubscriber2 DataMediumDewaxer1 = new DataSubscriber2(); DataSubscriber2 DataFastDewaxer1 = new DataSubscriber2(); #endregion // public MainForm() { InitializeComponent(); // #region Set Comm & Subscriber Properties & Items if (initalizeSub == false) { #region Set IP Addresses, Poll Rates, And Subscription Comms // Dewaxer Comms CommSlowDewaxer1.IPAddress = CommDewaxerIPAddress; CommSlowDewaxer1.PollRateOverride = CommSlow; // CommMediumDewaxer1.IPAddress = CommDewaxerIPAddress; CommMediumDewaxer1.PollRateOverride = CommMedium; // CommFastDewaxer1.IPAddress = CommDewaxerIPAddress; CommFastDewaxer1.PollRateOverride = CommFast; // // Bind Dewaxer Data Subscribers to Comms DataSlowDewaxer1.ComComponent = CommSlowDewaxer1; DataMediumDewaxer1.ComComponent = CommMediumDewaxer1; DataFastDewaxer1.ComComponent = CommFastDewaxer1; #endregion // #region DataSubscribers (Continuation) // NOTE: This is two different ways of adding elements programmatically // // Example 1 // This is one way of adding individual tags to the data subscriber during creation of the project // and then adding these items to the subscriber in the form // NOTE: You can create these items during runtime as well (like with a button press) PLCAddressItem Dewaxer1Temperature = new PLCAddressItem("N7:10", 1, "D1Temp", "Dewax 1 Temperature", 1, 1); PLCAddressItem Dewaxer2Temperature = new PLCAddressItem("N7:11", 1, "D2Temp", "Dewax 2 Temperature", 1, 1); // // Bind the PLC elements to the subscriber DataSlowDewaxer1.PLCAddressValueItems.Add(Dewaxer1Temperature); DataSlowDewaxer1.PLCAddressValueItems.Add(Dewaxer2Temperature); // // Example 2 // This is the other way. Create an array of a set number and then add in the form PLCAddressItem[] DewaxerSlow = new PLCAddressItem[2]; // 2 item array (0 index) // // Initalize all of the PLC elements for (int i = 0; i < DewaxerSlow.Count(); i++) { DewaxerSlow[i] = new PLCAddressItem(); } // // Set the PLC elements DewaxerSlow[0].PLCAddress = "N7:0"; // Actual Address or tag name in the processor DewaxerSlow[0].Description = "Example"; DewaxerSlow[0].Name = "Test"; // DewaxerSlow[0].ScaleOffset = 2; // This will offset the PLC value by plus 2 (NOTE: may use this if a sensor value is reading constantly offset) DewaxerSlow[0].ScaleFactor = .50; // This will divide the PLC value by half (NOTE: may use this if you have to convert to a percentage) // DewaxerSlow[1].PLCAddress = "N7:2"; DewaxerSlow[1].Description = "Example2"; DewaxerSlow[1].Name = "Test2"; DewaxerSlow[1].ScaleOffset = 2; DewaxerSlow[1].ScaleFactor = .50; // // add all of the PLC elements to the subscriber for (var i = 0; i < DewaxerSlow.Count(); i++) { DataSlowDewaxer1.PLCAddressValueItems.Add(DewaxerSlow[i]); } // // Subscriptions have been initalized initalizeSub = true; #endregion } #endregion } #region DataSubscribers (Set Data) #region Slow Subscriptions private void DataSlowDewaxer1_DataChanged(object sender, MfgControl.AdvancedHMI.Drivers.Common.PlcComEventArgs e) { if (e.ErrorId == 0) { if (e.PlcAddress == "N7") { // map the value of this // lbl_example.Text = e.Values[0]; } } } #endregion #region Medium Subscriptions private void DataMediumDewaxer1_DataChanged(object sender, MfgControl.AdvancedHMI.Drivers.Common.PlcComEventArgs e) { if (e.ErrorId == 0) { if (e.PlcAddress == "N7") { // map the value of this // lbl_example.Text = e.Values[0]; } } } #endregion #region Fast Subscriptions private void DataFastDewaxer1_DataChanged(object sender, MfgControl.AdvancedHMI.Drivers.Common.PlcComEventArgs e) { if (e.ErrorId == 0) { if (e.PlcAddress == "N7") { // map the value of this // lbl_example.Text = e.Values[0]; } } } #endregion #endregion } }